103BCommunication
10.2 PROFINET
Table 10- 22 Data types for the parameters
Parameter and type
REQ
Input
INTERFACE
Input
CONF_DATA
Input
DONE
Output
BUSY
Output
ERROR
Output
STATUS
Output
ERR_LOC
Output
The IP configuration information is placed in the CONF_DATA data block, along with a
Variant pointer on parameter CONF_DATA referenced above. The successful execution of
the T_CONFIG instruction ends with the handover of the IP configuration data to the network
interface. Errors, such as conflicts between IP addresses, are assigned to the diagnostic
buffer and written to the diagnostics buffer.
Table 10- 23 Condition codes for ERROR and STATUS
ERROR
STATUS
0
00000000
0
00700000
0
00700100
0
00700200
1
C08xyy00
1
C0808000
1
C0808100
1
C0808200
1
C0808300
1
C0808400
1
C0808600
1
C0808700
1
C0808800
422
Data type
Bool
HW_Interface
Variant
Bool
Bool
Bool
DWord
DWord
Description
No error
The job is not finished (BUSY = 1).
Start of job execution
Intermediate call (REQ irrelevant)
General failure
LADDR parameters for identification of the interface are invalid.
LADDR parameters for identification of the interface have been assigned a non-supported
hardware interface.
CONF_DATA parameter error: Data type of the Variant pointer does not match the data
type Byte.
CONF_DATA parameter error: The area pointer is not in the DB of the Variant pointer.
CONF_DATA parameter error: The Variant pointer is the wrong length.
Reserved
Inconsistency in the CONF_DATA data block length to the IP configuration
The parameters of the CONF_DATA data block field_type_id are invalid. (Only
field_type_id = 0 is allowed.)
Description
Starts the instruction on the rising edge.
ID of network interface
Reference to the structure of the configuration data;
CONF_DATA is defined by a System Data Type (SDT).
0: Job has not yet started or is still running.
1: Job was executed without error.
0: The job is complete.
1: The job is not yet complete. A new job cannot be
triggered.
Status parameters with the following values:
0: No error
1: Error occurred during processing. STATUS provides
detailed information on the type of error.
Status information including error information. (Refer to
the Error and Status condition codes in the table below.)
Fault location (field ID and subfield ID of the error
parameter)
System Manual, 11/2011, A5E02486680-05
S7-1200 Programmable controller