4.2
Parameters
Parameters of the AQ 4xU/I ST
The effective range of the parameters depends on the type of configuration. The following
configurations are possible:
● Central operation with an S7-1500 CPU
● Distributed operation on PROFINET IO in an ET 200SP system
● Distributed operation on PROFIBUS DP in an ET 200SP system
When assigning parameters in the user program, use the "WRREC" instruction to transfer
the parameters to the module using the data records; refer to the section Parameter
assignment and structure of the parameter data record (Page 31).
The following parameter settings are possible:
Table 4- 2
Settable parameters and their defaults (GSD file)
Parameters
Diagnostics
No supply voltage L+
Diagnostics:
Short-circuit
1
Diagnostics
Overflow
Diagnostics
Underflow
Diagnostics
wire break
2
Output type/range
Reaction to CPU STOP
Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1)
Manual, 03/2016, A5E03573365-AD
Value range
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
deactivated
•
Voltage +/- 10 V
•
Voltage +/- 5 V
•
Voltage 0..10 V
•
Voltage 1..5 V
•
Current +/- 20 mA
•
Current 0 - 20 mA
•
Current 4 - 20 mA
•
Turn off
•
Keep last value
•
Output substitute value
•
Default
Configuration
in RUN
Disable
yes
Disable
yes
Disable
yes
Disable
yes
Disable
yes
Current 4 -
yes
20 mA
Turn off
yes
Parameters/address space
4.2 Parameters
Effective range with configuration
software, e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
Channel
Channel
Channel
Module
17