Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook page 253

Table of Contents

Advertisement

[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-10
Error Code [7130]
1. Error code definition
Incompatible unit combination
2. Error definition and error detection method
The check code will appear when the indoor units with different refrigerant systems are connected.
3. Error source, cause, check method and remedy
Error source
Outdoor unit
90
- chapter 7
Cause
The connected indoor unit is for use with R22,
R407C, or R410A.
The M-NET connection adapter is connected
to the indoor unit system in a system in which
the Slim Model (A control) of units are con-
nected to the M-NET.
Indoor units that are incompatible with the
HVRF system are connected.
Check method and remedy
Check the connected indoor unit model.
Check whether the connecting adapter for
M-NET is not connected to the indoor unit.
(Connect the M-NET adapter to the central-
ized control system.)
BS_07_E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents