Error Code [5110] - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents

Advertisement

[7-7 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
3. Cause, check method and remedy
(1)
Thermistor failure
(2)
Pinched lead wire
(3)
Torn wire coating
(4)
A pin on the male connector is missing or
contact failure
(5)
Disconnected wire
(6)
Thermistor input circuit failure on the control
board
<Reference>
Short detection
TH2
70°C [158°F] and above (0.4kΩ)
TH3
110°C [230°F] and above (0.4kΩ)
TH4
240°C [464°F] and above (0.57kΩ)
TH5
70°C [158°F] and above (0.4kΩ)
TH6
70°C [158°F] and above (1.14kΩ)
TH7
110°C [230°F] and above (0.4kΩ)
TH15
110°C [230°F] and above (0.4kΩ)
7-7-3

Error Code [5110]

1. Error code definition
Heatsink temperature sensor (THHS) fault (Detail code 01)
2. Error definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Cause
(1)
INV board failure
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
52
- chapter 7
Cause
If the problem recurs when the unit is put into operation, replace the INV board.
Check method and remedy
Check thermistor resistance.
Check for pinched lead wire.
Check for wire coating.
Check connector.
Check for wire.
Check the intake temperature of the sensor with the LED
monitor.
When the temperature is far different from the actual temper-
ature, replace the control board.
Open detection
-40°C [-40°F] and below (130kΩ)
-40°C [-40°F] and below (130kΩ)
0°C [32°F] and below (698kΩ)
-40°C [-40°F] and below (130kΩ)
-40°C [-40°F] and below (130kΩ)
-40°C [-40°F] and below (130kΩ)
-40°C [-40°F] and below (130kΩ)
Check method and remedy
BS_07_E