[8-13 Parts Replacement Instructions ]
3. XL-module
Left rear heat exchanger
Front of the unit
Figure 1
(1) Remove the two front panels from the unit by unscrewing the 14 screws. (See Figure 2.)
(2) Remove the fin guard by unscrewing the 12 screws. (See Figure 2.)
(3) Remove pipe cover. (See Figure 3.)
(4) Remove the left drain pan by unscrewing the two screws and cutting the two cable ties. (See Figure 3.)
(5) Remove the right drain pan by unscrewing the 2 screws. (See Figure 3.)
(6) Remove the 3 cable straps from the center pillar. (See Figure 4.)
Fin guard
Center pillar
Front panel
Figure 2
(7) Remove the 3 cable straps holding motor wiring from the control box. (See Figure 5.)
(8) Remove the fan guard by unscrewing the 12 screws. (See Figure 6.)
(9) Remove the wire from the center frame. (See Figure 7.)
(10) Remove the motor ASSY by unscrewing the 8 screws, using caution not to damage the motor wiring or the fan. (See
Figure 7.)
Motor cable strap
Figure 5
112
- chapter 8
Right rear heat exchanger
Front heat exchanger
Drain pan (left)
Pipe cover
Figure 3
Fan guard
Fan
Figure 6
Drain pan (right)
Figure 4
Center frame
Motor ASSY
Figure 7
Cable strap for holding
strong electrical wiring
Cable strap for holding
weak electrical wiring
Compressor
cable strap
Motor ASSY
Fan
Motor cable strap
BS_08_E