[8-6 Troubleshooting Solenoid Valve Problems ]

8-6

Troubleshooting Solenoid Valve Problems

Check whether the output signal from the control board and the operation of the solenoid valve match.
Setting the self-diagnosis switch (SW4) as shown in the figure below causes the ON signal of each relay to be output to the LED's.
Each LED shows whether the relays for the following parts are ON or OFF. LEDs light up when relays are ON.
The circuits on some parts are closed when the relays are ON. Refer to the following instructions.
SW4 (SW6-10:OFF)
SW4
ON
1
2
3
4
5
6
7
8
9 10
SW4
ON
1
2
3
4
5
6
7
8
9 10
ON
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
2
3
4
5
6
7
8
9 10
1
When a valve malfunctions, check if the wrong solenoid valve coil is not attached the lead wire of the coil is not disconnected,
the connector on the board is not inserted wrongly, or the wire for the connector is not disconnected.
(1) 21S4a (4-way switching valve)
About this 4-way valve
When not powered:
Conducts electricity between the oil separator outlet and heat exchanger 1 (front heat exchanger), and between the gas ball
valve (BV1) and the accumulator to complete the circuit for the cooling cycle.
When powered:
The electricity runs between the oil separator and the gas ball valve, and between the heat exchanger and the accumulator.
This circulation is for heating.
Check the LED display and the intake and the discharge temperature for the 4-way valve to check whether the valve has no
faults and the electricity runs between where and where. Do not touch the pipe when checking the temperature, as the pipe
on the oil separator side will be hot.
Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.
(2) 21S4b (4-way switching valve), 21S4c (4-way switching valve) (21S4c is only on the (E)M500
models.)
About this 4-way valve
When not powered:
Conducts electricity between the oil separator outlet and heat exchanger 2 (rear or right heat exchanger) (<21S4b>), and be-
tween the oil separator outlet and heat exchanger 3 (left exchanger) (<21S4c>) and opens and closes the heat exchanger
circuit for the heating and cooling cycles.
When powered:
The electricity runs between the heat exchanger and the accumulator, and the valve opens or closes the heat exchanger cir-
cuit when cooling or heating.
Whether the valve has no fault can be checked by checking the LED display and the switching sound; however, it may be
difficult to check by the sound, as the switching coincides with 21S4b or 21S4c. In this case, check the intake and the dis-
charge temperature for the 4-way valve to check that the electricity runs between where and where.
Do not touch the valve when checking the temperature, as it will be hot.
Do not give an impact from outside, as the outer hull will be deformed leading to the malfunction of the inner valve.
22
- chapter 8
LD1
LD2
Upper
21S4a
SV10
Lower
Upper
Lower
Display
LD3
LD4
LD5
SV1a
21S4b
21S4c
SV14
SV15
LD6
LD7
LD8
SV2
SV11
SV9
BS_08_E