Checking The Error-Detection Circuit On The Pump Inv Board (Without Load); Checking The Pump Inv Board For Damage (Without Load) - Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook

Table of Contents

Advertisement

[8-10 Troubleshooting Inverter Problems ]
8-10-11
Checking the Pump Motor for Ground Fault and Coil Resistance Problems
Items to be checked
Remove pump motor winding. Check
insulation resistance and coil resis-
tance.
8-10-12

Checking the Error-Detection Circuit on the Pump INV Board (Without load)

Items to be checked
<INV32>
1)
Disconnect the inverter output
wiring from the INV board termi-
nals (SC-U, SC-V, SC-W).
2)
Operate the outdoor unit and
the hydro unit.
8-10-13

Checking the Pump INV Board for Damage (Without load)

Items to be checked
<INV32>
1)
Disconnect the inverter output
wiring from the INV board termi-
nals (SC-U, SC-V, SC-W).
2)
Set SW 1-1 on the INV board to
ON.
3)
Operate the outdoor unit and
the hydro unit.
Wait until the inverter output fre-
quency is stabilized, and then
check the inverter output volt-
age.
BS_08_E
Phenomena
1)
Pump motor insulation failure.
If < 1 MΩ, Defect.
2)
Pump motor wire failure.
Target coil resistance: Approx. 10 Ω.
(Changes with temperature)
Phenomena
1)
IPM/overcurrent cut-off error occurs.
Check code: 4250
Detail code: 101, 104, 105, 106, 107,
128
2)
Logic error occurs.
Check code: 4220
Detail code: 111
3)
Sensor-related circuit error occurs.
Check code: 5301
Detail code: 117, 127
4)
Open-circuited IPM error occurs.
Check code: 5301
Detail code: 119
Phenomena
1)
Inverter-related error is detected.
2)
Inverter voltage is not output.
3)
Line voltage imbalance of at least 5%
or 5 V occurs.
4)
No line voltage imbalance exists.
Remedy
Replace the pump
Replace the pump
Remedy
Replace the INV board.
Replace the INV board.
Replace the INV board.
Normal
Remedy
Set SW 1-1 on the INV board to
OFF, and go to [8-10-12 Checking
the Error-Detection Circuit on the
Pump INV Board (Without load)].
Replace the INV board.
Replace the INV board.
Normal
*Check the voltage, and set SW 1-1
on the INV board to OFF.