Mitsubishi Electric PUHY-M200YNW-A1 Service Handbook page 123

Table of Contents

Advertisement

[5-1 Dipswitch Functions and Factory Settings ]
(2) Additional dipswitch settings at time of shipment
Switch
SW4
1-10
SW6-10:
1:ON, 0:OFF
OFF
No.769
1000000011
No.817
1000110011
No.832
0000001011
No.848
0000101011
No.891
1101111011
No.896
0000000111
No.897
1000000111
No.900
0010000111
No.912
0000100111
No.913
1000100111
No.915
1100100111
SW4
1-10
[0:OFF,
1:ON]
No.916
0010100111
(Note 1)
SW6-10:ON
No.918
0110100111
No.921
1001100111
No.922
0101100111
No.933
1010010111
No.934
0110010111
No.964
0010001111
No.982
0110101111
No.988
0011101111
No.997
1010011111
No.1006
0111011111
4
- chapter 5
Function according to switch setting
Function
OFF (LED3 Unlit)
Self-diagnosis/operation moni-
tor
Test run mode: ON/OFF
Stops all ICs
Starts up drive recorder
Enabled
Cumulative compressor opera-
Retained
tion time deletion
Continuous heating cycle func-
Disabled
tion
Smooth auto-shift startup mode
Disabled
OC
Retained (IC/OC)
Clearance of error his-
tory
OS
Retained (OS)
Depends on the combined setting with No. 900
High sensible heat operation
(Note 3)
setting
(Factory setting: OFF)
Depends on the combined setting with No. 897
High sensible heat operation
(Note 3)
setting
(Factory setting: OFF)
Pump down function
Normal control
Forced defrost (Note 2)
Normal control
(E)P200 - 300:
Defrost start temperature (Note
-13°C [9°F]
2)
(E)P350 - 500:
-11°C [12°F]
(E)P200 - 300:
Defrost end temperature (Note
10°C [50°F]
2)
(E)P350 - 500:
7°C [45°F]
Changes the defrost timer set-
50 minutes
ting (Note 2)
Temperature unit display
°C
Refrigerant amount adjustment
Normal control
Effective only when
TH7 ≤ 5 is true or the
Snow sensor setting
snow sensor contact
input is on.
Continuous fan op-
Snow sensor setting
eration (FAN=50%)
Depends on the setting combination with No.
Target evaporation tempera-
982 (Note 4)
ture setting
(Factory setting: OFF)
Depends on the setting combination with No.
Target evaporation tempera-
964 (Note 4)
ture setting
(Factory setting: OFF)
Refrigerant recovery/Evacua-
Disabled
tion (LEV2, LEV1, SV2 open)
Multiple-stage low-noise set-
See note 7 below.
ting
(Factory setting: OFF)
Switch setting timing
ON (LED3 Lit)
Anytime after power on
Sends a test-run signal
Anytime after power on
to all IC
Disabled
Anytime after power on
Any time after being energized (When changed
Cleared
from OFF to ON)
After being energized and while the compressor
Enabled
is stopped
After being energized and while the compressor
Enabled
is stopped
Deleted (IC/OC)
Anytime after power on (OFF→ON)
Deleted (OS)
After being energized and while the compressor
is stopped
After being energized and while the compressor
is stopped
After being energized and while the compressor
Pump down operation
is stopped
Anytime after power on
10 minutes after the completion of defrost oper-
Forced defrost starts
ation (OFF→ON) or 10 minutes after compres-
sor start-up (OFF→ON)
-8°C [18°F]
Anytime after power on
5°C [41°F]
Anytime after power on
90 minutes
Anytime after power on (OFF→ON)
°F
Anytime after power on
Anytime after power on (except during initial
Refrigerant amount ad-
startup/becomes ineffective 90 minutes after
just mode
compressor started up.)
Effective when TH7 ≤ 5
Anytime after power on
is true
Intermittent fan opera-
tion (The fan operates
in the cycle of being in
operation at 100% ca-
Anytime after power on
pacity for 5 minutes and
then stops and remains
stopped for 30 min-
utes.)
Anytime after power on
Anytime after power on
After being energized and when units are
Enabled
stopped
After power on and while the compressor is
stopped
BS_05_E