[7-9 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
7-9-9
Error Code [7117]
1. Error code definition
Model setting error
2. Error source, cause, check method and remedy
Error source
Outdoor unit
(1)
(2)
Hydro unit
BS_07_E
Cause
Wiring fault
Loose connectors, short-circuit, con-
tact failure
Loose connectors, short-circuit, con-
tact failure
Check method and remedy
(Detail code 15)
1)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code 14)
1)
Check the connector CNTYP4 on the control board for
proper connection.
(Detail code 12)
1)
Check the connector CNTYP2 on the control board for
proper connection.
2)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code 16)
1)
Check the connector CNTYP on the INV board for
proper connection.
2)
Check the connector CNTYP5 on the control board for
proper connection.
3)
Check the wiring between the control board and INV
board.
Refer to the following page(s). [7-2-1 Error Code
[0403]]
(Detail code 0, 1, 5, 6)
1)
Check the wiring between the control board and INV
board.
Refer to the following page(s). [7-2-1 Error Code
[0403]]
2)
Check the settings of SW5-3 through SW5-6 on the
control board.
3)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code Miscellaneous)
*If a set-model-name identification error occurs, check
the detail code on the unit on which the error occurred.
The detail code that appears on other units will be dif-
ferent from the ones shown above.
Check the connector CN403 on the control board for
proper connection.