Checking The Fan Board Error Detection Circuit At No Load; Checking The Fan Board For Damage At No Load - Mitsubishi Electric PUHY-HP72 Service Handbook

Table of Contents

Advertisement

[8-9 Troubleshooting Inverter Problems ]
8-9-7

Checking the Fan Board Error Detection Circuit at No Load

Items to be checked
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
(2)
Disconnect the output wiring
to the fan motor.
Disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
(3)
Turn on the breaker.
(4)
Operate the unit.
8-9-8

Checking the Fan Board for Damage at No Load

Items to be checked
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
(2)
To allow for the disconnection
of output wiring from the fan
motor, disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
(3)
Set SW7-2 on the control
board to ON. On a model with
two fan motors, set SW7-2
(left fan when seen from the
front) or SW7-4 (right fan
when seen from the front) to
ON.
(4)
Turn on the breaker.
(5)
Operate the unit
HWE18240_GB
Phenomena
1)
An error other than current sensor er-
ror (5305, 5306: Detail code 135) is
detected during operation.
2)
Current sensor fault
Error code: 5305, 5306
Detail code: 135
Phenomena
1)
An error other than the current sen-
sor error (5305, 5306 Detail code
135) is detected within 30 seconds
from the startup of operation.
2)
Inter-wire voltage imbalance of 5 V or
above
3)
No inter-wire voltage imbalance ex-
ists. A current sensor error (Detail
code 135) is detected 30 seconds af-
ter the startup of operation, and the
operation stops.
Remedy
Replace the fan board.
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
Remedy
Replace the fan board.
Replace the fan board.
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.