Operating Guide | VLT® Compressor Drive CDS 803
Fault
Alarm/
Fault text
num‐
warning
ber
bit num‐
ber
80
29
Drive initialised
87
47
Auto DC Brak-
ing
95
40
Broken Belt
99
Locked rotor
126
Motor Rotating
200
Fire Mode
202
Fire Mode Lim-
its Exceeded
250
New spare part
251
New Typecode
42 | Danfoss A/S © 2019.12
Warn‐
Alarm
Trip
ing
lock
X
X
X
X
X
X
X
X
X
X
X
X
Cause of problem
All parameter settings are initialized to default settings.
The drive is auto DC braking.
Torque is below the torque level set for no load, indicat-
ing a broken belt. See parameter group 22-6* Broken Belt
Detection.
The rotor is locked or the load is too high.
High back EMF voltage. Stop the rotor of the PM motor.
Fire mode has been activated.
Fire mode has suppressed 1 or more warranty voiding
alarms.
The power or switch mode power supply has been ex-
changed. Contact the local Danfoss supplier.
The drive has a new type code. Contact the local Danfoss
supplier.
AQ321748767627en-000101 / 130R0570