Operating Guide | VLT® Compressor Drive CDS 803
4.4 Start-up Quick Guide for Compressor Closed-loop Applications
0-01 Language
1
[0]
English
0-06 Grid Type
2
Size related
0-60 Main Menu Password
3
[0]
1-13 Compressor Selection
4
Size related
1-00 Configuration Mode
5
[0]
Open loop
3-02 Minimum Reference
6
30
Hz
3-03 Maximum Reference
7
Hz
200.000
3-10 Preset Reference
8
[0] 0.00 %
3-15 Reference 1 Source
9
[1]
Analog in 53
3-41 Ramp 1 Ramp Up Time
10
90.00
s
3-42 Ramp 1 Ramp Down Time
11
30.00
s
5
5-12 Terminal 27 Digital Input
12
[2]
Coast inverse
5-40 Function Relay 1
13
[0] [9]
Alarm
6-19 Terminal 53 mode
14
[1]
Voltage mode
6-10 Terminal 53 Low Voltage
15
0.07
V
6-11 Terminal 53 High Voltage
16
10.00
V
6-14 Terminal 53 Low Ref./Feedb.
17
Size related
6-15 Terminal 53 High Ref./Feedb.
18
200.000
Hz
6-29 Terminal 54 mode
19
[0]
0.00
Current mode
6-22 Terminal 54 Low Current
20
4.00
mA
6-23 Terminal 54 High Current
21
20.00
mA
6-24 Terminal 54 Low Ref./Feedb.
22
0.000
0
6-25 Terminal 54 High Ref./Feedb.
23
50.000
20-00 Feedback 1 Source
24
[0]
0.00
No function
20-81 PI Normal/Inverse control
25
[0]
Normal
8-01 Control Site
26
[0]
Digital and ctrl.word
8-30 Protocol
27
[0]
FC
8-32 Baud
28
[2]
9600 Baud
Illustration 15:
Closed-loop Quick Guide