6.4.2 Formula to calculate the expansion vessel pre-pressure
6.4.3 To check the water volume and flow rate
ERGA04~08DAV3(A) + EHVZ04+08S18+23DA6V+9W7
Daikin Altherma 3 R F
4P618957-1 – 2020.03
▪
Domestic hot water tank – After installation. Immediately after installation, the
domestic hot water tank must be flushed with fresh water. This procedure must
be repeated at least once a day the first 5 consecutive days after installation.
▪
Domestic hot water tank – Standstills. In cases where during longer periods of
time there is no consumption of hot water, the equipment MUST be flushed with
fresh water before usage.
▪
Domestic hot water tank – Disinfection. For the disinfection function of the
domestic hot water tank, see "8.5.6 Tank" [
▪
Thermostatic mixing valves. In accordance with the applicable legislation, it may
be necessary to install thermostatic mixing valves.
▪
Hygienic measures. The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
▪
Recirculation pump. In accordance with the applicable legislation, it may be
required to connect a recirculation pump in between the hot water end point
and the recirculation connection of the domestic hot water tank.
a
b
a
Recirculation connection
b
Hot water connection
c
Shower
d
Recirculation pump
▪
Valve towards expansion vessel. The valve towards the expansion vessel (if
equipped) MUST be open.
The pre-pressure (Pg) of the vessel depends on the installation height difference
(H):
Pg=0.3+(H/10) (bar)
The indoor unit has an expansion vessel of 10 litre with a factory-set pre-pressure
of 1 bar.
To make sure that the unit operates properly:
▪
You must check the minimum and maximum water volume.
▪
You might need to adjust the pre-pressure of the expansion vessel.
Minimum water volume
There are no requirements for the minimum water volume.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be
required.
4
132].
c
d
6
Preparation
|
Installer reference guide
47