15.2 Input modify to RTD
Plug 2 pcs of Jumper in the left slot as shown
Notes
When input is thermocouple or PT100, it has been calibrated and tested at the factory, we don't recommend customers to make
Their own calibration.
FY operation manual
Jumper Position
RTD calibration flowchart
Start
SET 2_2 = 1
TRCL = 0
TRCH = 5FFF
INP1 = PT1
USPL = 850.0
LSPL = -199.9
Input PT100 signal -199.9°C
Adjusts "TRCL" until PV = -199.9
Input PT100 signal 850.0°C
Adjusts "TRCH" until PV = 850.0
Input -199.9°C Check the PV = -199.9
Input 850.0°C Check the PV = 850.0
NO
OK ?
YES
Repeat step A~E 3~4 times
NO
OK ?
YES
End
Set the range you want
Ex: Low = 0.0 , High = 200.0
Set LSPL = 0.0 , USPL = 200.0
Software Setting
Parameter set as"INP1=PT1~PT3"
to display TRCL & TRCH
Step A
Step B
Step C
Step D
Step E