Example(4) only use SOAK_B (ALD1=19)
Boot completed, the alarm1 is OFF, and the PV is directly controlled at 100 °C. when the PV reaches 100 °C, the temperature is kept
for 10 minutes. after 10 minutes alarm is turned ON and the control function keep ON
Parameter setting
Level
Parameter
1
SV
3
ALD1
1
SOAK(AL1)
PV time chart
AL1 time chart
FY operation manual
Set value
100.0
10
00.10
Temperature
100.0
Temperature rise
Alarm=OFF
25.0
5
seconds
Action
ON
OFF
Description
Target temperature
AL1 as soak timer
Soak for 10 minutes
Time up
Alarm=ON
PV
SOAK
10 minutes
time
time
52