14.5 Output Calibration Proccedure Diagram
69
Output1 Signal (4mA~20mA) calibration flowchart
Start
SET4_4=1
CLO1=0
CHO1=3600
Set controller
output%=0%
Adjust CLO1 until meter=4mA
Set controller
output%=100%
Adjust CHO1 until meter=20mA
Set controller output%=0% and check meter=4mA
Set controller output%=100% and check meter=20mA
NO
OK?
End
Display CLO1 and CHO1
Default Value
SV=LSPL low setpoint
SV=USPL high setpoint
YES
FY operation manual