11.3 Remote SV

Description
Remote SV functions as an analog signal (4~20mA or 0~10V) generated by external devices (EX: PLC AO module, transmitter)
to the Remote SV terminal of the controller, to change the SV with a preset range.
Remote SV signal selection: 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Function Diagram
E l e c t r i c
f u r n a c e
Parameter
Parameter
Symbol
SET0.3
INP2
ANL2
ANH2
Examples
Input signal is K1 and its range is -50.0~600.0. When an external analog signal is input to the Remote SV
terminal, the signal will be based on the range presents linear display of SV parameters
When the signal input value is less than 2.4mA, the PV position shows nnn2, indicating that the signal of Remote SV is lower than
the lower limit value
When the signal input value is greater than 21.6mA, the PV position shows uuu2, indicating that the signal of Remote SV is higher
than the upper limit value
Remote SV upperer limit +10%
Remote SV upper limit
Remote SV lower limit
Remote SV lower limit -10%
Parameter setting
Level
Parameter
Set value
4
SET0.3
4
INP2
3
ANL2
3
ANH2
0x657C
FY operation manual
PV
SV
OUT1
OUT2
AT
AL1
AL2
AL3
S e n s o r i n p u t
OUT1
0
20
40
60
SET A/M
TAIE
C o n t r o l
o u t p u t
+
-
SSR
Content
0 : Remote SV disable
1 : Remote SV enable
Sub input type selection
0 : none
1 : 10~50mV / 4~20mA / 1~5V /
2~10V
(only available in remote SV)
2 : 0~50mV / 0~20mA / 0~5V /
0~10V
(only available in remote SV)
3 : valve feedback
4 : CT input
Sub input zero calibration
Sub input span calibration
(hex display)
Remote SV
4.0
2.4 (-10%)
1
1
Remote SV signal low point calibration value
744
(each controller calibrate value is different)
Remote SV signal high point calibration value
(each controller calibrate value is different)
MAN
PRO
%
Remote SV input
80
100
FY900
P L C A O m o d u l e / transmitter
P o w e r
Range
MAX
MIN
1
0
4
0
9999
-1999
0x7FFF
0x0000
20.0
21.6 (110%)
Description
Enable Remote SV function
Remote SV signal=4~20mA
mA
Default
Level
0
Level 4
0
Level 4
0
Level 3
0x5FFF
Level 3
mA
Hide/
Display
---
---
SET2.4
SET2.4
42