Multimaster Function; Systems With Two Or More Outlet-Pressure Sensors; Description Of Functions For The System; Settings - Grundfos Hydro Multi-E Series Installation And Operating Instructions Manual

Table of Contents

Advertisement

10.2.1 Home display
1
Status Settings Assist
Setpoint
Control mode
Const. pressure
5.00 bar

Operating mode

Actual controlled value
Normal
9
8
7
Fig. 34 Example of Home display
Pos.
Symbol
Description
Home
This menu shows up to four user-defined
parameters. You can select parameters
1
shown as shortcut icon
pressing
display for the selected parameter.
Status
This menu shows the status of the pump
2
-
and system as well as warnings and
alarms.

Settings

This menu gives access to all setting
parameters. You can make detailed
3
-
settings of the pump in this menu.
See section
pumps.
Assist
This menu enables assisted pump setup,
4
-
provides a short description of the control
modes and offers fault advice.
Indicates that the pump has been stopped
5
via the
Indicates that the pump is functioning as
6
master pump in a multipump system.
Indicates that the pump is functioning as a
7
slave pump in a multipump system.
Indicates that the pump is operating in a
8
multipump system. See section
13.11 "Multi-pump
Indicates that the function to configure
9
settings has been disabled for safety
reasons. See section
2
3
4
4.90 bar
6
5
, and when
you go directly to the "Settings"
13. Description of functions for
button.
setup".
"Buttons on
product".

11. Multimaster function

11.1 Systems with two or more outlet-pressure
sensors
If two or more pumps in the system are configured with an
outlet-pressure sensor (standard option), they can all function as
master pumps. As standard, the pump with the lowest number will
be the master pump. From factory, the master pump is marked
with number 1.
If master pump 1 is switched off or stopped due to an alarm, one
of the other master pumps will automatically take control of the
system.

12. Description of functions for the system

Hydro Multi-E offers the following functions via Grundfos Go
Remote or the advanced control panel.
12.1 Settings
12.1.1 Setpoint
You can set the setpoint for all control modes when you have
selected the desired control mode. See section
mode.
Factory setting
See section
29. Factory
settings.
12.2 Operating mode
The operating modes are the operating conditions that the
booster system can be brought in by the user.
Possible operating modes:
"Stop"
All pumps stop.
"Normal" (factory setting)
One or more pumps are operating to maintain the set
pressure.
"Max."
All pumps run at maximum speed.
The operating modes can be selected on the control panel, with
Grundfos GO Remote or via bus.
12.2.1 Normal operation
H
H set
H
set
Fig. 35 Hydro Multi-E in normal operation, meaning
constant-pressure mode
In constant-pressure mode, Hydro Multi-E adjusts its
performance to the desired setpoint.
12.3 Control
Q
19