6.7.2 Connection terminals, CME pumps
The CME pump has these connections:
two analog inputs
two digital inputs or one digital input and one open-collector
output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
See fig. 14.
Digital input 1 is factory-set to be the start-stop input
when open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV) to ensure protection against
electric shock.
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC to the
output.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
Mains supply (terminals N, PE, L or L1, L2, L3, PE).