Controller
8. Switch to the next list item, "Max. pressure deviation".
–
This parameter is meaningless in the master and can be ignored.
–
Define the parameter in the slaves.
–
Setting range 0.1 – 5.0 bar.
–
Use the arrow keys to enter the parameter value.
–
Press "OK" to confirm.
9. Switch to the next list item, "Activation delay".
–
The activation delay sets the activation behaviour of the optional second pump,
compressor or overflow valve.
–
This parameter is meaningless in the master and can be ignored.
–
Define the parameter in the slaves.
–
Setting range 0–240 seconds.
–
Use the arrow keys to enter the parameter value.
–
Press "OK" to confirm.
10. Switch to the next list item, "Max. level deviation".
–
This parameter is meaningless in the master and can be ignored.
–
Define the parameter in the slaves.
–
Setting range 0 – 20 %.
–
Use the arrow keys to enter the parameter value.
–
Press "OK" to confirm.
11. Switch to the next list item, "Block message 29 PFK".
–
Use the arrow keys to select each function.
NO:
Select this function for the master.
The "29 Communication fault" message is output to the floating contact.
YES:
Select this function for the slaves.
The "29 Communication fault" message is not output to the floating
contact.
–
Press "OK" to confirm.
Note!
You have completed the settings in the controllers when all parameters for the master and the slaves are entered.
–
Ensure that all devices are set to Master/Slave operation.
12 — English
Master/Slave Operation — 24.09.2015
Max. pressure deviation:
dPmaxSL = 1.0 bar
Activation delay:
LK/MK = 5 s
Max. level deviation:
dNiv = 5 %
Message 29 PFK
Block?