Reflex Variomat Service Instructions Manual page 12

Master/slave operation
Hide thumbs Also See for Variomat:
Table of Contents

Advertisement

Controller
8. Switch to the next list item, "Max. pressure deviation".
This parameter is meaningless in the master and can be ignored.
Define the parameter in the slaves.
Setting range 0.1 – 5.0 bar.
Use the arrow keys to enter the parameter value.
Press "OK" to confirm.
9. Switch to the next list item, "Activation delay".
The activation delay sets the activation behaviour of the optional second pump,
compressor or overflow valve.
This parameter is meaningless in the master and can be ignored.
Define the parameter in the slaves.
Setting range 0–240 seconds.
Use the arrow keys to enter the parameter value.
Press "OK" to confirm.
10. Switch to the next list item, "Max. level deviation".
This parameter is meaningless in the master and can be ignored.
Define the parameter in the slaves.
Setting range 0 – 20 %.
Use the arrow keys to enter the parameter value.
Press "OK" to confirm.
11. Switch to the next list item, "Block message 29 PFK".
Use the arrow keys to select each function.
NO:
Select this function for the master.
The "29 Communication fault" message is output to the floating contact.
YES:
Select this function for the slaves.
The "29 Communication fault" message is not output to the floating
contact.
Press "OK" to confirm.
Note!
You have completed the settings in the controllers when all parameters for the master and the slaves are entered.
Ensure that all devices are set to Master/Slave operation.
12 — English
Master/Slave Operation — 24.09.2015
Max. pressure deviation:
dPmaxSL = 1.0 bar
Activation delay:
LK/MK = 5 s
Max. level deviation:
dNiv = 5 %
Message 29 PFK
Block?
NO