11.3 ABB Drive Selection Guidelines

ABB Basic drive selection criteria apply with Permanent Magnet Synchronous
Motors. Select an ACH580 drive so that all criteria below are met:
1.
Rated drive current I2N is de-rated by ambient, altitude and switching
frequency*
2.
Motor rated current is less than or equal to the rated drive current I2N of the
drive
3.
Maximum required motor current is below 1.5 x rated drive current
4.
Maximum required motor current is suitable for drive overloading**
5.
Average required motor power is less than rated drive power PN
6.
Maximum required motor power is less than 1.5 x rated drive power
7.
Maximum required motor power is suitable for drive overloading**
*
For drive de-rating see ABB User's Manuals
** Maximum current with 110% overload allowed for one minute every ten
minutes Maximum current with 150% overload allowed for one minute every ten
minutes. ABB drives can supply maximum output current I2max for 2 seconds at
start.

11.4 Motor Setup Parameters with ABB Drives

The following parameters should be set based on nameplate data of the EC
Titanium™ Motor. It is important to accurately input these values for proper
motor control. The ACH580 ID run (Parameter 99.13) is used to setup motor
values for Resistance, Ld and Lq and these values are not required for startup.
ABB Drive
Parameter
99.03
99.04
99.06
99.07
99.08
99.09
99.10
99.13 (ID Run)
99.13 (ID Run)
99.13 (ID Run)
MN448
Function
Motor Type
Control Mode
Rated Current (A)
Motor BEMF Voltage
Motor Rated Frequency
(Hz)
Motor Speed
Motor Rated Power (kW)
Motor Resistance Rs
Motor Inductance Ld
Motor Inductance Lq
Drive Setting
Permanent Magnet
Vector
Nameplate Value
Nameplate Value
Nameplate Value
Nameplate Value
Nameplate Value
Auto Tune
Auto Tune
Auto Tune
Standalone Motor and ABB Drive Setup 11-3