9.4 Modbus control mode (1103 = 3 or 4), Parameter 9902 Settings

9902
Digital input 1
0, 2, 4,
Open: Stop (disable)
8...13
Closed: Run (enable)
Open: Stop (disable)
1
Closed: Run (enable)
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
5
Closed: Run (enable)
Open: Stop (disable)
6
Closed: Run (enable)
Open: Stop (disable)
7
Closed: Run (enable)
Open: Stop (disable)
14
Closed: Run (enable)
Note: If 1100= 2, 3, 6 or 7, start/stop will be controlled by digital input 1 and communication trip will be disabled. (Exception if 9902 = 5, 6 and
7, see comments). For further information on the MODBUS RTU Register Map information and communication setup please refer to
Appendix E.
9.5 User PI control mode: (1103 = 5 or 6), Parameter 9902 Settings
9902
Digital input 1
0, 2,
Open: Stop (disable)
9...13
Closed: Run (enable)
1
Open: Stop (disable)
Closed: Run (enable)
3, 7
Open: Stop (disable)
Closed: Run (enable)
4
Normally Open (NO)
Momentary close to run
5
Normally Open (NO)
Momentary close to run
6
Normally Open (NO)
Momentary close to run
8
Open: Stop (disable)
Closed: Run (enable)
14
Open: Stop (disable)
Closed: Run (enable)
MN448
Digital Input 2
Digital Input 3 (An in 2)
No effect
No effect
No effect
No effect
Open: Master speed ref
External trip/thermistor input:
Closed: Preset speed 1
Open: Trip, Closed: Run
Open: Master speed ref
Open: Preset speed 1
Closed: Preset speed 1/2
Closed: Preset speed 2
Open: Master speed ref
External trip/thermistor input:
Closed: Analog input
Open: Trip, Closed: Run
Open: Master speed ref
External trip/thermistor input:
Closed: keypad speed ref
Open: Trip, Closed: Run
External trip/thermistor input:
No effect
Open: Trip, Closed: Run
Digital Input 2
Digital Input 3 (An in 2)
Open: PI control
No effect
Closed: Preset speed 1
Open: PI control
No effect
Closed: Analog input 1
Open: PI control
External trip/thermistor input:
Closed: Preset speed 1
Open: Trip, Closed: Run
Normally Closed (NC)
No effect
Momentary open to stop
Normally Closed (NC)
Open: PI control
Momentary open to stop
Closed: Preset Speed 1
Normally Closed (NC)
External trip/thermistor input:
Momentary open to stop
Open: Trip, Closed: Run
Open: Forward
PI feedback analog input
Closed: Reverse
No effect
External trip/thermistor input:
Open: Trip, Closed: Run
Digital input 4 (An in 1)
Comments
Digital input 1 must be closed for the
No effect
drive to run. Start and stop commands
given via the RS485 link
Default speed reference is PI controller
No effect
speed reference
Connect external thermistor type PT100
No effect
or similar to digital input 3
No effect
When digital input 2 open, start & stop
controlled via Modbus. When digi in 2
Analog input reference
closed, drive auto runs if digi in 1 closed,
and comms loss control will be disabled.
No effect
No effect
Digital input 4 (An in 1)
Comments
No effect
Digital input 1 must be closed for the
drive to run.
Analog input 1
No effect
Connect external thermistor type PT100
or similar to digital input 3
No effect
No effect
No effect
No effect
Digital input 1 must be closed for the
drive to run.
No effect
Control Modes 9-6