7.4 Quick Start Keypad Control

When delivered, the EC Titanium software parameters are in the factory default state, except for the motor data which was
pre-loaded at the factory with parameters that are optimum for the performance of the Motor. A full list of parameters &
default values can be found in Chapter 10.
Step 1
Perform Mechanical and Electrical installation as per Chapters 3 and 4.
Step 2
Connect the Remote Keypad as per Chapter 5.
Step 3
Set 1103 Primary Command Source = 1 to allow the EC Titanium to be controlled from the keypad in a for-
ward direction only, or = 2 to allow forward and reverse operation.
Step 4
Reference Chapter 6 on details on how to navigate the keypad.
Step 5
Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open (drive dis-
abled).
Step 6
Switch on the supply to the EC Titanium, Press and hold the
parameter view mode and set Parameter 1103 Primary Command Source Mode = 1 or 2.
Step 7
Enable the drive by closing the switch between control terminals 1 & 2.
The keypad display will show
Step 8
Press the
The value of the digital potentiometer will be displayed, indicating the target speed.
Use the
Press the STOP key to return to the real time display showing "
Step 9
Press the
increasing speed until the target speed is reached. During operation the speed of the drive can be changed in
real time by simply using the
Step 10
STOP the motor, PRESS the (Stop) Key and disable the drive by opening the control switch (terminals 1-2).
CAUTION: If the potentiometer is turned to zero with the enable closed, the display will show
still active waiting for a speed reference to re-accelerate. If left at zero reference for >= 20 seconds the
drive will go into standby mode, display shows
Reverse Direction of Rotation (Parameter 1103 = 2)
While in operation press the
as set in the forward direction unless the Up or Down arrows change the set speed value.
CAUTION: Whenever the drive is started, it will start with a positive speed unless the direction is negated by the
digital inputs on the user terminals. See Chapter 9 Control Modes for setup instructions.
MN448
SToP
.
(Stop) key, the display shows
(Up) and
(Down) keys to select the required target speed.
(Start) key to start the drive ramping up to the target speed. The drive will run forward,
(Up) and
(Start) key. The motor will reverse its direction of rotation. Target speed will be the same
navigate key for > 1 second to enter
H 0.0.
. and the last digit should be flashing.
SToP
".
(Down)arrows.
StandbY
, waiting for a speed reference signal.
H 0.0.
. The drive is
Quick Startup Guide 7-3