9.3 Keypad Mode: (1103 = 1 or 2) Parameter 9902 Settings
9902
Digital input 1
0,
Open: Disable
8...13
Closed: Enable
Open: Stop (disable)
1
Closed: Run (enable)
Open: Disable
2
Closed: Enable
Open: Stop (disable)
3
Closed: Run (enable)
Open: Stop (disable)
4
Closed: Run (enable)
Open: Stop (disable)
5
Closed: Run (enable)
Open: Stop (disable)
6
Closed: Run (enable)
Open: Fwd Stop
7
Closed: Fwd Run
Open: Stop (disable)
14
Closed: Run (enable)
NOTES (keypad mode):
1.
When changing from other speed reference (e.g. preset speed or analog speed) back to keypad speed reference (digital pot value) while
drive is running, the following behaviour will be expected:
If 1100 = 0 or 2, digital pot speed value will be set to minimum speed 2007 to start with.
If 1100 = 1 or 3, digital pot will keep unchanged from last time adjustment.
If 1100 = 4 or 6, digital pot value will be updated to be the same as current motor running speed.
If 1100 = 5 or 7, digital pot value will be set to the same value as preset speed 4 to start with.
2.
When drive is not running:
If 1100 = 0, 2, 4 or 6, digital pot speed value will be set to minimum speed 2007.
If 1100 = 1 or 3, digital pot will keep unchanged.
If 1100 = 5 or 7, digital pot value will be set to the same value as preset speed 4.
3.
If 1100 = 2, 3, 6 or7, closing digital input 1 (or digital input 2 if 9902 = 7) will start the drive (Auto-run). The keypad START and STOP button
will not function in this case. The keypad speed can still be adjusted using the UP and DOWN buttons.
4.
If 1103 = 1, reverse speed can only be achieved by using preset speed or analog input speed. Reverse speed can also be achieved when
using reverse run terminal input. Reverse speed cannot be selected via the local or remote keypad.
5.
Where both Remote Up and Remote Down push button inputs are available, closing both inputs will start the drive
6.
There is no single-step delay when using the remote push-buttons to change the speed. This delay is only implemented when using the
drive keypad directly.
9.3.1 Keypad Control Mode MOP (E-Pot Controls)
Keypad Control Mode (1103 = 1 or 2), Digital Input Function Select (9902 = 2)
This is the digital input configuration when the drive is controlled using the keypad and a MOP input is required. It provides
a remote up and remote down MOP control for speed increase and decrease with a run disable and forward reverse input.
Keypad controls remain active.
Keypad controls remain active
Closed input 2 enables the drive.
A momentary closed input 3 will increase speed and
a momentary closed input 4 will decrease speed.
Terminal 6 input is used to reverse the drive
direction.
9-5 Control Modes
Digital Input 2
Digital Input 3 (An in 2)
Closed: remote UP push-
Closed: remote DOWN push-
button
button
No effect
No effect
Closed: remote UP push-
Closed: remote DOWN push-
button
button
Closed: remote UP push-
External trip/thermistor input:
button
Open: Trip, Closed: Run
Closed: remote UP push-
Open: Keypad speed ref
button
Closed: Analog input 1
Open: Forward run
Open: Keypad speed ref
Closed: Reverse run
Closed: Analog input 1
Open: Forward run
External trip/thermistor input:
Closed: Reverse run
Open: Trip, Closed: Run
Open: Reverse stop
External trip/thermistor input:
Closed: Reverse run
Open: Trip, Closed: Run
External trip/thermistor input:
No effect
Open: Trip, Closed: Run
9902 = 2
Digital input 4 (An in 1)
Comments
Open: Forward
Factory Default 9902 = 0
Closed: Reverse
Default speed reference is PI
No effect
controller speed reference
Open: Keypad speed ref
Closed: Preset speed 1
Closed: remote DOWN
Connect external thermistor type
push-button
PT100 or similar to digital input 3
Analog input 1
Analog input 1
Open: Keypad speed ref
Connect Ext thermistor type PT100
Closed: Preset speed 1
or similar to Digi input 3
Open: Keypad speed ref
Closing digital inputs 1 and 2
Closed: Preset speed 1
together carries out a fast stop
Connect external thermistor type
No effect
PT100 or similar to digital input 3
MOP Control
1
+24V User Input
O: Stop (Disable)
2
C: Run (Enable)
3
C: Remote Up
4
C: Remote Down
5
+10 Volts
O: Forward
6
C: Reverse
7
0 Volts
MN448