Advanced Parameter Group - ABB EC Titanium Series Manual

Table of Contents

Advertisement

10.3 Advanced Parameter Group

The following tables describes the parameters that are visible in the
Parameters in the Long parameter mode
Index
Name/Selection
2017
Maximum Current Limit
0.1...175.00
2105
DC Injection Speed
0.0...2008
2106
DC Injection Current
0.0...100.0
2301
Vector Mode Gain
0.0...200.0
2605
Operating Mode Select
0: Industrial Mode
1: Pump Mode
2: Fan Mode
9903
Motor Control Mode
0
1
2
3
9910
Motor parameter
Autotune
WARNING:
Autotune should not
be performed on this
product.
0: Disable
1: Enable
10-16 Parameter Definitions
PA-A
Description
Defines the max current limit in vector control modes.
Sets the speed at which DC injection current is applied during braking to
Stop, allowing DC to be injected before the drive reaches zero speed if
desired.
Sets the level of DC injection braking current applied according to the
conditions set in 2104 and 2105.
Single Parameter for Vector speed loop tuning. Affects P & I terms
simultaneously. Not active when 9903 = 1.
Provides a quick set up to configure key parameters according to the
intended application of the drive. Parameters are preset according to the
table.
Current
Setting
Application
Limit (2017)
0
General
1
Pump
2
Fan
Intended for general purpose applications.
Intended for centrifugal pump applications.
Intended for Fan applications.
Selects the motor control method. For proper control of the EC
Titanium parameter 9903 should be set to 2 (PM Control).
Vector speed control mode
V/HZ Mode
PM Motor Vector Speed Control
BLDC Motor Vector Speed Control
Autotune is disabled in the ECM software however it can be
accessed through the keypad.
In the event an Autotune is performed it will affect performance and
possibly make the IMD inoperable. To recover the motor specific
parameters will need to be loaded. The necessary parameters
and their values can be obtained by scanning the QR Code on the
motor with a smart device or you can access the parameters from
the ECM software under the File menu (allows the parameter set to
be downloaded from the web).
WARNING: Autotune should not be performed on this product.
Drive immediately carries out a non-rotating autotune, parameter
9910 MOTOR PARAMETER AUTO-TUNE ENABLE returns to 0
when completed.
mode (Advanced Parameters).
Torque
Characteristic
(2610 & 2611)
150%
Constant
110%
Variable
110%
Variable
Default
110 %
0.0 Hz/Rpm
20 %
50 %
2
Spin Start
(2101)
0: Off
0: Off
2: On
2
0: Disable
MN448