4.3.1 Fuse / Circuit Breaker Selection
Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line,
according to the data in Table 4-2 Electrical Ratings. The fuses must comply with any local codes or regulations in place. In
general, type gG (IEC 60269) or UL type J fuses are suitable; however, in some cases type aR fuses may be required.
Check that the operating time of the fuse is below 0.5 seconds. The operating time depends on the fuse type, the supply
network impedance as well as the cross sectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with gG fuses, ultra-rapid (aR) fuses in most cases reduce the operating time to an acceptable
level.
Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilized in
place of fuses, providing that the clearing capacity is sufficient for the installation.
The maximum permissible short circuit current at the drive input power terminals as defined in IEC60439-1 is 5kA.
The rated fuse currents given in the table are the maximums for the mentioned fuse types. If smaller fuse ratings are use,
check that the fuse rms current rating is larger than the rated input amps shown in the rating tables in Chapter 2.
Drive Type
Top (T) / Axial (A)
1-phase 100V...115V AC (+/-10%) - 3 Phase 230V Output
ECS100T/A 1H1DF4
1-phase 200...240V AC (+/-10%) - 3 Phase 230V Output
ECS100T/A 8H1DF4
ECS100T/A 8H2DF4
ECS100T/A 8H3DF4
ECS100T/A 8H3EF4
3-phase 200...240V AC (+/-10%) - 3 Phase 230V Output
ECS100T/A 2H1DF4
ECS100T/A 2H2EF4
ECS100T/A 2H3DF4
ECS100T/A 2H3EF4
ECS100T/A 2H5EF4
3-phase 380...480V AC (+/-10%) - 3 Phase 460V Output
ECS100T/A 4H1DF4
ECS100T/A 4H2DF4
ECS100T/A 4H3DF4
ECS100T/A 4H3EF4
ECS100T/A 4H5EF4
ECS100T/A 4H7EF4
ECS100T/A 4H7FF4
ECS100T4H10FF4
1. Cable sizes shown are the maximum possible that may be connected to the drive. Cables should be selected according
to local wiring codes or regulations applicable at the point of installation.
2. Refer to the UL Online Certification Directory for a list of UL Recognized products, File Number E226333.
3. The integral overload protection does not provide branch circuit protection. Branch circuit protection must be provided in
accordance with applicable local regulations and the National Electrical Code.
4. Fuse type: UL JDDZ Class J.
5. Where permitted, equivalent circuit breakers may be used.
4-4 Electrical Installation and Planning
Table 4-2 Fuse & Wire Size Electrical Specifications
Power
Nominal Input
(HP)
Current (A)
1
15.1
1
12.9
2
12.9
3
12.9
3
12.9
1
7.5
2
7.5
3
12.9
3
12.9
5
10.5
1
3.5
2
3.5
3
5.6
3
5.6
5
7.5
7.5
11.5
7.5
12
10
12
Fuse UL (Class J)
or MCB (Type B)
Non UL
UL
2,3,4
25
20
16
17.5
16
17.5
16
17.5
16
17.5
10
10
10
10
16
17.5
16
17.5
16
15
6
6
10
10
10
10
10
10
10
10
16
15
16
15
16
15
Maximum
Nominal
Cable Size
Output
(AWG) 1
Current
14
3.2
14
7.0
14
7.0
12
7.0
12
7.0
14
4.3
14
4.3
14
7.0
14
7.0
10
10.5
14
2.2
14
2.2
14
4.1
14
4.1
14
5.8
12
9.5
12
12.0
10
12.0
MN448