Long Parameter Group - ABB EC Titanium Series Manual

Table of Contents

Advertisement

10.2 Long Parameter Group

The following tables describes the parameters that are visible in the
sequential listing of all available parameters.
Parameters in the Long parameter mode
No.
Name/Value
0000
READ ONLY PARAMETERS
0102
Rotor Speed
(Estimated)
0104
Motor Current
0107
DC BUS VOLTAGE
0109
APPLIED MOTOR VOLTAGE
0110
INTERNAL HEATSINK
TEMPERATURE
0111
SPEED REFERENCE INPUT
0115
KWh/MWh METER
0120
ANALOG INPUT 1 APPLIED
SIGNAL LEVEL
0121
ANALOG INPUT 2 APPLIED
SIGNAL LEVEL
0126
PI CONTROLLER OUTPUT
0140
HOURS RUN METER
0150
INTERNAL DRIVE
TEMPERATURE
0160
DIGITAL INPUT STATUS
0183
DC BUS VOLTAGE RIPPLE
LEVEL
0188
OPERATING TIME
ACCUMULATED WITH
HEATSINK TEMPERATURE
ABOVE 85°C
0189
OPERATING TIME
ACCUMULATED WITH
AMBIENT TEMPERATURE
ABOVE 80°C
10-4 Parameter Definitions
PA-
Description
Pressing the NAVIGATE key when the
enter into the Read only status parameter list shown below. Initially
is shown and using the UP and DOWN Arrows will scroll to the required
Read only status parameter. Pressing NAVIGATE once more on the will then
display the value of that particular Read only status parameter.
For those parameters which have multiple values (e.g. software ID
parameter 3301), pressing the UP and DOWN keys will display the different
values within that parameter.
Pressing NAVIGATE returns to the next level up. If NAVIGATE is then
pressed again (without pressing UP or DOWN), the display changes to the
next level up (main parameter level, i.e. Parameter "
In vector control mode, this parameter displays the estimated rotor speed
of the motor.
8 most recent values prior to trip, updated every 250ms
Displays the instantaneous DC Bus Voltage internally within the drive in V
DC. (0...1000V dc)
Displays the instantaneous output voltage from the drive to the motor V AC.
(0...600V AC)
Temperature of heatsink in °C (-20 ... 100 °C)
Displayed in Hz if Parameter 9908 MOTOR RATED SPEED = 0, otherwise
displayed in RPM. (-2008 ... 2008)
Total number of KWh/MWh consumed by the drive.
Displays the signal level applied to analog input 1 (Terminal 6) in % after
scaling and offsets have been applied.
Displays the signal level applied to analog input 2 (Terminal 4) in % after
scaling and offsets have been applied.
Displays the output level of the PI controller in %.
Not affected by resetting factory default parameters.
(0 to 99 999 hours)
Actual internal ambient temperature in °C
Binary value.
Displays the status of the drive inputs, starting with the left hand side digit
= Digital Input 1 etc.
Displays the level of ripple present on the DC Bus Voltage in V DC. This
parameter is used by the ACS255 for various internal protection and
monitoring functions.
Displays the amount of time in hours and minutes that the ACS255 has
operated for during its lifetime with a heatsink temperature in excess of
85°C. This parameter is used by the ACS255 for various internal protection
and monitoring functions. (HH:MM:SS)
Displays the amount of time in hours and minutes that the DRIVE
has operated for during its lifetime with an ambient temperature in
excess of 80°C. This parameter is used by the DRIVE for various
internal protection and monitoring functions. (HH:MM:SS)
mode (Long Group Parameters) that contain a
0000
parameter is displayed will
00
0000
").
Default
Fault history
(read-only)
MN448