Cisco 6100 Installation Procedures Manual page 15

Thermal upgrade kit

Advertisement

Disconnect the Cisco 6100 Power Connections
To disconnect the Cisco 6100 power connections, complete the following steps:
Note
If you do not have 12 AWG wire installed, you will replace these wires with a larger gauge
wire later in the procedures.
Step 1
Use a socket driver or a Phillips-head screwdriver to remove the clear cover over the Cisco 6100
power connections.
Disconnect the wires connecting the Cisco 6100 chassis to the fuse and alarm panel (POS RTN and
Step 2
NEG DC connections) as shown in Figure 2 (dual-power feed) and Figure 3 (single-power feed).
These wires will be replaced with a larger gauge wire later in the procedures.
Figure 2
NEG
Cisco 6100/6130
78-10158-01
Power Return Connections for the Cisco 6100—Dual-Power Feed
1 2 3 4 5 6 7 8 9 10
NEG DC
B
1 2 3 4 5 6 7 8 9 10
POS
POS RTN
1 2 3 4 5 6 7 8 9 10
NEG DC
A
1 2 3 4 5 6 7 8 9 10
POS RTN
P13
Cisco 6100 Thermal Upgrade Kit Installation Procedures
Installing the Cisco 6100 Thermal Upgrade Kit
NEG
POS
15