TM 225/A
6

Operating behavior

6.1

Response by the measurement inputs

Internally the TM 225/A measures the temperature value every 1 ms. The slid-
ing mean value from the last 100 measurements (100 ms) is calculated every
2 ms. This value is available at the hardware end point system.TI0 for the
application.
6.2

Behavior during a fault

6.2.1

Response to module errors

In case of a module error an internal watchdog monitor will be triggered. The
module signals the module error to the CPU module or bus link module.
6.2.2

Sensor failure

The module identifies both a failure in the measurement line, as well as in the
reference currency line. The sensor failure is passed on to the CPU. Once the
sensor failure has been corrected the status "Sensor failure" will be automat-
ically reset.