daviteq WS433-M12F-ATE User Manual page 6

Sub-ghz wireless ambient temperature sensor
Table of Contents

Advertisement

a: constant (default value is 1)
b: constant (default value is 0)
So, if there is no user setting for a and b ==> Y = X
The Y value will be compared with Lo and Hi threshold.
Status bytes of sensor Node
Hi-Byte is error code
Error code
0
1
2
3
4
Lo-Byte is sensor type
Error code
0
1
2
3
4
Logic status of parameters
Hi-Byte is Logic status of parameter 1
If parameter 1's value > high threshold 1 => Hi-Byte of Logic status = 1
If parameter 1's value < low threshold 1 => Hi-Byte of Logic status = 0
If parameter 1 is digital => Hi-Byte of Logic status = parameter 1's value
Timer up 1 = (Total time when Hi-Byte of Logic status = 1)
Timer down 1 = (Total time when Hi-Byte of Logic status = 0)
RisingEdge counter 1 = (Counter value when Hi-Byte of Logic status changes from 0 to 1)
FallingEdge counter 1 = (Counter value when Hi-Byte of Logic status changes from 1 to 0)
Lo-Byte is Logic status of parameter 2
If parameter 2's value > high threshold 2 => Lo-Byte of Logic status = 1
If parameter 2's value < low threshold 2 => Lo-Byte of Logic status = 0
If parameter 2 is digital => Lo-Byte of Logic status = parameter 2's value
Timer up 2 = (Total time when Lo-Byte of Logic status = 1)
Timer down 2 = (Total time when Lo-Byte of Logic status = 0)
RisingEdge counter 2 = (Counter value when Lo-Byte of Logic status changes from 0 to 1)
FallingEdge counter 2 = (Counter value when Lo-Byte of Logic status changes from 1 to 0)
Ambient Temperature Sensor Module (ATE)
Description
No error
Just exchange the sensor module but node has not been reset ==> please take out the
battery for 20s then install it again to reset node to recognize the new sensor module
Error, sensor port M12F shorted to GND
Error, sensor port M12F shorted to Vcc
Error, sensor port M12F shorted each other
Description
No error
Just exchange the sensor module but node has not been reset ==> please take out the
battery for 20s then install it again to reset node to recognize the new sensor module
Error, sensor port M12F shorted to GND
Error, sensor port M12F shorted to Vcc
Error, sensor port M12F shorted each other