Maintenance-Object Repair Procedures
Table 8-512. Test #887 Read and Clear Board Counters — Continued
Error
Test
Code
Result
Description / Recommendation
256,
FAIL
The active IPSI circuit pack's Packet Interface circuit has an error counter set.
512,
The following error codes are possible: 256 (parity error), 512 (FIFO
768
overflow), 768 (parity error and FIFO overflow error).
1. If error code 256 or 768 is reported, the IPSI's Packet Interface circuit
8-1264
Issue 1 May 2002
received a parity error off the packet bus.
a. Check for alarms logged against the packet bus. See
(Packet Bus)'' on page 8-1230
b. Check for alarms and errors logged against other circuit packs
connected to the PN's packet bus. A list of packet circuit packs is
presented in the first section of this repair procedure. Refer to the
repair procedures for those circuit packs, in this manual, to clear those
errors first.
c. If this is a standard- or duplex-reliability system, replace the circuit
pack at a time that would cause the least disruption of service. The
circuit pack is still functional but should be replaced.
d. If this is a high- or critical-reliability system and if the Packet Interface
circuit is on the standby IPSI, replace the circuit pack.
e. If this is a high- or critical-reliability system and if the Packet Interface
circuit is on the active IPSI, enter set ipserver interface to perform a
planned IPSI interchange. Replace the standby IPSI circuit pack.
''PKT-BUS
to clear those errors first.
Continued on next page
555-233-143