997-434-000-4, Issue 4
May 2010
ID2000 Series Operating Manual
PANEL STATUS: FAULT
This condition occurs for a number of reasons: some
arise from incorrect operation of a remote sensor or
module, others from incorrect operation of the panel or
system as a whole.
Also included in this category are 'POWER SUPPLY
FAULT', which indicates a failure of battery, mains supply
or charger circuit, and 'SYSTEM FAULT' which indicates
a microprocessor fault.
The FAULT condition continues to be shown until
superseded by a higher-priority condition or until cleared
by pressing the RESET pushbutton.
The occurrence may have been 'accepted' at the panel
by pressing the ACCEPT pushbutton, if so the status is
still 'FAULT'.
The indications of the panel and external equipment are
as follows:
LAMP indications:
POWER (green):
EARTH FAULT/
POWER SUPPLY FAULT/
SYSTEM FAULT LAMP (amber):
(as appropriate):
Numbered zone indication(s) (for zone(s) where
sensor/module faults have been detected - amber):
if not accepted:
if accepted:
The LCD displays the message shown below:
Status: **FAULT**
(location) (device type) or (fault identification)
For approximately two minutes after Fault is accepted,
line 2 shows a scrollable message (use
scroll) giving full details about the FAULT:
(type of fault) (Device number) (zone) (type) (analogue
value at time of fault) (location) (date & time of fault)
as applicable, plus indication as to whether any further
faults exist, indicated by 'MORE: PRESS
A1 - 6
if mains or battery power OK: ON
if not accepted:
FLASHING
if accepted:
STEADY
FLASHING
FLASHING
(date)
(time)
and
to
or
'.