Honeywell NOTIFIER ID2000 Series Operating Manual page 20

Hide thumbs Also See for NOTIFIER ID2000 Series:
Table of Contents

Advertisement

5 SECONDS
FIRE
EN54-2 : 10.1b. Automatic
cancellation of walk tests
must not be configured
ID2000 Series Operating Manual
The following checks allow certain devices to be easily
checked for correct operation:
a. Analogue sensors - observe that the sensor's LED
changes to steady ON status, returning to pulsing
mode about 5 seconds after the test condition is
removed.
b. Manual Call Points - the appropriate sounder outputs
are activated (according to the specified test
requirements), either for approximately one second,
or for as long as the call point test key is left in
(depending on configuration). Only the internal
sounder circuits and outputs designated as type BELL
are involved.
A test may be applied to any point any number of times;
test alarms are auto-resetting. Wait at least 5 seconds
before re-testing a device.
To cancel testing:
1 Press
only):
0=TEST
3=SET CLOCK 4=CONFIGURE 5=ALARM COUNT
2 From the above display, press pushbutton '0' to display
the TEST menu once more. Again press the '0'
pushbutton to select 'Zone'. The display will be:
CANCEL TEST MODE: (
3 Press
This action must be carried out before another zone
can be put into Test mode.
Test mode may also be cancelled if:
a. A FIRE is detected in another Zone (if so configured
[default] - non-EN54-2 : 10.1 b).
b. If the walk round test is not completed within the time
limit specified for the installation (normally 2 hours) if
configured (non-EN54-2 : 10.1 b).
17
. The following is displayed (for a short time
1=DIS/ENABLE 2=LOG/DISPLAY
! ! ! ! !
/X)?
and the system returns to normal operation.
997-434-000-4, Issue 4
May 2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents