Appendix B: Compatible Devices
FA-106 and FA-103 Underwriters Laboratories Canada ULC Listed 2-Wire Smoke
Detectors
Notes:
• Reset time, hold for five seconds minimum.
• Total standby current of all detectors must not exceed 3 mA.
• Two-wire smoke detectors can be mixed or matched with different models on the
same Initiating Circuit as long as the total standby current of all detectors does not
exceed 3mA.
Make Model / Base
Mircom
MIR-525
MIR-525T
Apollo
Series 60A Bases 45681-200,-220,-232,-251
Series 65A Bases 45681-255,-256,-257,-258
55000-325
55000-326
55000-327
55000-328
Hochiki
DCD-135/HSC-220R
DCD-135/NS6-220
DCD-190/HSC-220R
DCD-190/NS4-220
DCD-190/NS6-220
SU-24/HSC-220R
SU-24/NS4-220
SU-24/NS6-220
SLR-24/HSC-220R
SLR-24/NS4-220
SLR-24/NS6-220
14
Maximum # of
devices per
circuit
System Sensor i3
30
C2W-BA c/w base
30
C2WT-BA c/w base
System Sensor
1400A
2400A
30
1451A/B401BA
30
2451A/B401BA
30
1100
30
1151A/ B110LPA
1151A/ B116LPA
12
1451A/B401A
12
1451A/ B406BA
12
1451DH/ DH400
12
2100A
12
2100TA
12
2151A/ B110LPA
7
2151A/ B116LPA
7
2400THA
12
2451A / B401BA
12
2451A / B406BA
12
2451A / DH400
Make Model / Base
Maximum # of
devices per
circuit
30
30
30
25
25
25
25
25
25
25
25
25
30
30
15
25
25
25
25
25