Prior to Installation

Ensure:
1. That a suitable Automatic Fire Detection alarm system is installed.
2. A System X Site Survey has been completed.
3. System X transmitters have been installed according to the results of the Site Survey.
4. The fire door is self-closing i.e. has a door closer fitted.
5. The fire door closes tightly against the door jamb.
6. You have determined the closing force of the door.
2
7. Where Dorgard X
is to be fitted, the floor and door surfaces are smooth and flat.
8. There is clearance under the fire door for fitting of the Floorplate, i.e. 5mm.
9. The fire alarm system is working correctly, i.e. the CIE is not in fault state and the
sounders work when activated.
2
10. Dorgard X
forms part of your Fire Risk Assessment (as required by the Fire
Precautions [Workplace] Regulations 1997, also required by the Regulatory Reform (Fire
Safety) Order 2006).
2
Note. Dorgard X
will hold a door open once linked to its corresponding System
X transmitter.