Fire Alarm Test

1. Ensure all Dorgard X
fire doors open.
2. Check that the System X installation is
correct (refer to System X User Guide).
3. Set the CIE into fire alarm condition for a
minimum of 30 seconds.
2
4. Dorgard X
will release the fire door in approx.
20 seconds.
2
5. When Dorgard X
is ready to release the door,
it will sound a 'Hi Lo' warning tone repeated
8 times before releasing the door.
Note. Although System X conducts a self
test with Dorgard X
bell tests are highly recommended. This
will ensure that System X is responding
to your fire alarm.