Certification
6.2 EMC and Environmental Type Tests
•
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
44
If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Induced (Con-
ducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped
Oscillatory
Mains Frequen-
cy Voltage
Ripple on DC
Power Supply
Damped Os-
cillatory Wave
Voltage Dips
and Interrupts
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
AC and DC
Power Ports
DC Power Ports
Slow Damped
DC Power Ports
Test Levels
Severity Levels
±8 kV
±15 kV
20 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
10 V
100 A/m
Continuous
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
2.5 kV Common
1 kV Differential
Mode @1 MHz
30 V Continuous
300 V for 1s
10%
2.5 kV Common
Mode on Pow-
er and Signal
1.0 kV Differential
Mode on Power
30% for 0.1 s
RUGGEDCOM RSG2100
Installation Manual, 03/2020, C79000-G8976-1040-17
4
a
Note
a
Note
4
4
3
4
3
5
3
4
3
3
Need help?