Voltage Supply - JUMO mTRON T System Description

Measuring, control, and automation system
Hide thumbs Also See for JUMO mTRON T:
Table of Contents

Advertisement

NOTE!
The external voltage supply for the digital input/output module 12-channel and the voltage sup-
ply for controlling the digital inputs of this module must be switched on/off with a common dis-
connecting device (common electrical circuit).
6.3

Voltage supply

The DC 24 V voltage supply is provided by an external power supply unit and fed in via the
base unit (central processing unit) or a router module. For this purpose, these modules have a
2-pole terminal strip with Push-In technology that can be accessed from the front (1). The ter-
minal strip can be removed after releasing a screw connection.
The input/output modules are supplied with voltage via the side contacts (2) of the base unit or
router module.
The voltage supply for the multifunction panel – also DC 24 V – is to be fed in via a terminal
strip (11) on the multifunction panel. This also involves a 2-pole terminal strip with Push-In tech-
nology that can be removed after releasing the screw connection.
Voltage supply of a base unit, using the example of a central processing unit
1
Voltage supply In, DC 24 V
2
Voltage supply Out, DC 24 V
The router module has identical connections to the voltage supply (note the reversed arrange-
ment of the +24 V and GND terminals).
NOTE!
Only use the installation instructions or the operating manual of the affected module for the
electrical connection. Follow the safety information stated there.
Com1
ON
3
1
2
4
ON
1
2
3
4
Com2
6 Electrical connection
Power
Status
Bus Error
Com1
Com2
Setup
Run
Stop
Reset
LAN
Bus Out
1
2
55