SNMP Solo

Establish Network Communications

1. PING SNMP Solo.
Issue a PING command from the NMS. If you do not get a
response, check the SNMP Solo's network connection and
IP address.
2. Test the adapter with an NMS.
Perform a "get" command and a "set" command. If either
command fails, check the SNMP Solo access controls. The
manager must have read permission to execute a get
command successfully and read/write permission to
execute a set command successfully.
(See the Configuring the NMS section for a detailed
discussion.)
Your SNMP Solo SNMP adapter is now
24
Final Installation
If the SNMP Solo detects three communication
failures in a row, the red LED turns on and
stays on until the SNMP Solo receives a
successful communication from the UPS.
installed and completely functional.