Download Print this page

Specifications - Lutron Electronics PowPak FC-SENSOR Manual

Advertisement

Available languages

Available languages

LutronR

Specifications

PowPak
Fixture Sensor
®
Regulatory Approvals
• FC-SENSOR, FC-VSENSOR:
– cULus Listed
Power/Load
• Operating voltage: 12 V-
• Operating current: 25 mA
• IEC SELV / NECR Class 2
Environmental
• Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%–90% humidity, non-condensing;
indoor use only
Warranty
• 5 Year Limited Warranty. For additional Warranty
information, please visit: www.lutron.com/
TechnicalDocumentLibrary/Sensor_Warranty.pdf
Wiring
• Sensor wires are IEC SELV / NECR Class 2 rated
Settings
• Occupancy sensor timeout (fixture sensor): 15 minutes
• Utilizes a green laser pointer (by others, not a LutronR
product) to associate PicoR wireless controls and
Radio Powr Savr
sensors to PowPak
fixture controls via RF. See LutronR application note
#407 (www.lutron.com/GreenLaserAppNote) for more
information.
– Green laser specifications:
∙ Wave output: constant
∙ Wavelength: 532 nm
∙ Output power: 5 mW maximum
Sensor
Green Laser
S p e c i f i c at i o n S u b m i t ta l
®
Job Name:
Job Number:
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
wireless
®
!
WARNING
Eye injury and/or blindness hazard; avoid direct eye exposure to laser beam.
• Use of laser pointer is NOT recommended for use with LutronR products located near reflective surfaces.
• Do NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or
other shiny surfaces. Do NOT view the laser beam through binoculars, magnifying glass, or other optical devices.
• Do NOT allow children to use laser pointers.
• Read and follow the laser pointer manufacturer's instructions on safe use. In the event of injury, get
medical attention immediately.
Model Numbers:
• 2-wire connection between a PowPak
and a PowPak
wireless fixture control
®
– The wires are interchangeable to eliminate miswiring
– The sensor comes with 2 ft (0.6 m) of wires
– If hanging pendant fixtures, the maximum wire
length between fixture sensor and fixture control is
12 ft (3.7 m). Sensor should be mounted no more
than 2 ft (0.6 m) from the fixture.
Features
Occupancy Sensor:
• Passive infrared motion detection with exclusive LutronR
XCTT Technology for major and minor motion detection.
• 360˚ field-of-view.
• Up to 300 ft
(27.9 m
2
2
150 ft
(13.9 m
) minor motion coverage.
2
2
Daylight Sensor:
• Daylight sensor has simple, automatic calibration
out-of-the-box.
• Designed to give a linear response to changes in
perceived light level.
• Detects ambient light level changes from 0 to 1600 lx
(0 to 150 fc).
• Daylight compensation through LutronR reliable closed
loop proportional control. For more information,
see www.lutron.com/TechnicalDocumentLibrary/
daylighting_white-paper.pdf
DANGER
PowPak
Fixture Controls
®
369866c 4 09.10.15
fixture sensor
®
) major motion coverage and
page
4

Advertisement

loading

This manual is also suitable for:

Powpak fc-vsensorPowpak fcj-010Powpak fcj-eco