ELECTRICAL
REQUIREMENTS
(CONT.)
July 2014
An all pole, separate disconnect switch, with proper capacity fuses or
breakers must be installed at a convenient location between the fryer
and the power source, and must be installed according to national and
local codes.
It is recommended that a 30 mA rated protective device such as a re-
sidual current circuit breaker (RCCB), or ground fault circuit interrupter
(GFCI), be used on the fryer circuit.
Permanently connected electric fryers with casters must be installed
with flexible conduit and a cable restraint, when installed in the United
States. See illustration at left. Holes are available in the rear fryer frame
for securing the cable restraint to the fryer. The cable restraint does not
prevent the fryer from tipping.
DRYWALL CONSTRUCTION
Secure I-bolt to a building stud. Do
not attach to drywall only. Preferred
installation is approximately six inches
to either side of service. Cable restraint
must be at least six inches shorter than
flexible conduit.
The supply power cords shall be oil-resistant, sheathed flexible cable,
no lighter than ordinary polychloroprene or other equivalent synthetic
elastomer-sheathed cord. It should be an insulated copper conductor
rated for 600 volts and 90
use the next larger wire size. CE units require a minimum wire size of 6
mm to be wired to the terminal block.
7
C. For runs longer than 50 feet (15.24 m),