Cisco NCS 1004 Hardware Installation Manual page 23

Hide thumbs Also See for NCS 1004:
Table of Contents

Advertisement

Install Cisco NCS 1004
Figure 19: Rack Specification
Rack Type
19" racks
23" racks
ETSI racks
Note
The distance between the front and the rear post in a four post rack is 427 mm (closed position) and 707 mm
(open position).
Install NCS 1004 on an EIA/ANSI/ ETSI Rack
It is mandatory to fix the fiber management brackets for all the cards in the chassis before installing the Cisco
NCS 1004 chassis onto the rack. See
Rack Front Opening X
Rack Mounting Hole
Center-Center Y
450.8mm (17.75")
465mm (18.312")
552.45mm (21.75")
566.7mm (22.312")
500.0mm(19.68")
515.0mm(20.276")
Attach Fiber Management Bracket
Hardware Installation Guide for Cisco NCS 1004
Install NCS 1004 on an EIA/ANSI/ ETSI Rack
Mounting Flange
Dimension Z
482.6mm (19")
584.2mm (23")
533.4mm(21")
section for the detailed procedure.
21