2.1 Preparing for Installation

Choose a location for the NCD that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible
with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appro-
priate knockouts.
Before installing the fire alarm system, read the following:
Review the installation precautions at the front of this manual.
Installers should be familiar with the standards and codes specified in Section 1.1 "Standards and Specifications".
All wiring must comply with the National and Local codes for fire alarm systems.
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a separate battery cabinet; this space is for
internal battery installation.
Review installation instructions in Section 2.1 "Installation Checklist".
WARNING: Risk of irreparable equipment damage
!
Make sure to install system components in the sequence listed below. Failure to do so can damage the control panel and
other system components.
WARNING: Risk of irreparable equipment damage
!
Wear a static discharge strap on wrist to prevent equipment damage.
WARNING: ADJUSTING THE SCREEN BRIGHTNESS GREATER THAN 75% WILL REDUCE THE LIFE OF THE
!
DISPLAY.

2.2 Installation Checklist

The checklist that follows contains references to information included in other manuals; see "Related Documentation" on page 7 for doc-
ument part numbers.
1.
Mount the cabinet backbox to the wall.
2.
Attach NCD to dress panel.
3.
Attach option boards (e.g. network
communications modules and other devices of the
same size) to chassis and dress plates.
4.
Attach chassis in assembled dress plate to
cabinet.
5.
Wire Relays
6.
Digital Voice components.
7.
Network devices.
8.
Main power supply.
9.
Install main power supply and batteries. Run
cables to main and optional power supplies, DC
power outputs, relays, etc.
WARNING: DO NOT ACTIVATE POWER AT THIS TIME. DO NOT CONNECT BATTERIES.
10.
Check that all mounting holes are secured to insure a proper Earth Ground connection.
11.
Connect wire shielding to Earth Ground.
12.
Apply AC power to the power supply or the control panel.
Do NOT connect batteries until AC power is checked (see next step).
13.
Check AC power.
14.. Connect the batteries using interconnect cable as described in power supply manual.
15.
Install the dress panels, doors and covers.
16.
Program the NCD.
17.
Field test the system.
NCD Instruction Manual — P/N LS10210-051NF-E:C 2/18/2019

Section 2: Installation

Task
Section 2.3 "CAB-4 Series Cabinet"
Section 2.5 "Dress Plate Mounting"
Refer to the Installation document for the specific device and dress plates.
Section 2.3 "CAB-4 Series Cabinet"
Figure 2.6
Digital Voice Control Manual, etc.
Noti•Fire•Net Version 5.0 & Higher Manual, or High-Speed Noti•Fire•Net
Manual and/or Installation document for specific device(s).
Main Power Supply Manual
BB-100/200 Cabinet Installation Instructions.
Applicable system and power supply manuals.
Power Supply manual.
CAB-3/CAB-4 Series Cabinet Installation Document.
Section 3, "Programming", on page 20
Table 2.1 Installation Checklist
Refer to:
11