Section 1: Installation - Honeywell GAMEWELL LCD-SLP Product Installation Document

Liquid crystal display-smart loop panel
Table of Contents

Advertisement

Section 1: Installation

2.1 Standards
The LCD-SLP module complies and is intended to be installed in accordance with the following Standards:
National Fire Protection Association
• AHJ
• NFPA 70
UL Standards, UL 864 9th and 10th Edition
Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the
rollout of UL 10th edition (12/2/2018).
Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when
approved by the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL listing cards located on the UL online certification directory.
https://iq.ulprospector.com
2.2 Installation Requirements
Installers must be Gamewell-FCI Factory Certified to program this product. For additional information on this product, contact the
Gamewell-FCI Customer Support to schedule Factory Certified Training.
All components of the S3 Series and E3 Series Systems should be installed per the following requirements:
• Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that could cause
condensation. Equipment must be securely mounted on rigid, permanent walls.
• Operating temperature shall not exceed the range of 32° to 120° F (0 to 49° C).
• Operating humidity not to exceed 93% non-condensing at 90° F (32° C).
• There should be adequate space around the installation to allow easy access for operation and servicing.
• All sub-assemblies and components are to be located in compliance with local, national codes and the manufacturer's
recommendations.
• All installation field wiring shall be in compliance with local and national codes.
COLD WATER/EARTH GROUND STANDARD:
NOTE:
All modules must be connected to an earth ground connection. Failure to make a proper earth ground connection from a
metallic cold water pipe or driven ground rod will result in loss of surge protection, reduce the tolerance of the system to
transients, and will adversely affect the operation of the system. Panel neutral or conduit ground is not acceptable; minimum
wire size is 14 AWG.
2.3 LCD-SLP Assembly Installation Options
Table 2.3.1 lists the systems, cabinets, and mounting plates that use the LCD-SLP.
System Cabinets,
Inner/Outer Doors
S3 Series Cabinets
SLP-BB Cabinet, B Cabinet
S3 Series, B-Size Cabinet
E3 Series Inner Doors and Plates
Cabinet A2 Inner Door
E3BB-FLUSH-LCD Cab A2 Front Cover
CAB AA 2-Bay Inner Door
CAB B Inner Door
CAB C INCC-E3 Plate, 7-Bay Inner Door E3ID2-C
CAB D INCC CAB-D 13-Bay Inner Door
Retrofit Cabinets
B-Slim Cab Outer Door
600XL Retrofit Inner Door
7200 Cab-B Retrofit Inner Door
7200 Cab-C Retrofit Inner Door
®
E3 Series
is a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.
©2020 Copyright by Honeywell International Inc. All rights reserved.
2
Authority Having Jurisdiction • NFPA 72
National Electrical Code
Part Number
SLP-BB
E3BB-BB/RB
E3BB-BA2
E3BB-FLUSH-LCD CAB A2" 13 1/4"W x 10"H x 4.1/2"D
E3BB-BAA
E3ID2-B
E31D2-D
E3BB-RBSLIM
IF600-RETROFIT 600XL: 30"W x 22"H x 5.5"D
7200-B-RETROFIT 7200 CAB B:21"W x 28.5"H x 4"D
7200-C-RETROFIT 7200 CAB C:21"W x 38"H x 4"D
Table 2.3.1 LCD-SLP Assembly Installation Options
LCD-SLP Product Installation Document — P/N LS10045-000GF-E:E 12/16/2019
• NFPA 101
Cabinet
Dimensions
14.9"W x 21.5"H x 4.5"D
19 3/8"W x 19 3/8"H x 4.5"D
CAB A2: 13 1/4"W x 10"H x 4.1/2"D
CAB AA: 19 1/4"W x 10"H x 4.5"D
CAB B: 19 3/8"W x 19 3/8"H x 4.5"D Figure 2.7.2.1
CAB C: 19 3/8"W x 30"H x 4.5"D
CAB D: 19 3/8"W x 41"H x 4.5"D
B-SLIM: 14"W x 20"H x 4.5"D
National Fire Alarm Code
Life Safety Code
Figure that shows the
Installation Assembly
Figure 2.6.1.1
Figure 2.6.2.1
Figure 2.7.1.1.1
Figure 2.7.1.2.1
Figure 2.7.1.3.1
Figure 2.7.3.1
Figure 2.7.4.1
Figure 2.8.1.1
Figure 2.8.2.1
Figure 2.8.3.1
Figure 2.8.4.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents