ABB G13 User Manual page 67

Table of Contents

Advertisement

JSON Communication
Request
Description
Notes
Baudrate settings are not propagated to meters. This call changes baudrate in gate-
way only.
Users need to match settings in all meters using HMI of each meter.
Examples
G13
User Manual
POST /configuration/eqbus HTTP/1.1
Authorization: Basic XXXXXXXXXXXXXXX=
Content-Type:application/json
Content-Length: 46
{
"baudrate": 500000,
"interoctettimeout": 1000
}
[Int]: Supported baudrates are listed below
• baudrate
1200
2400
9600
19200
38400
57600
115200
125000
230400
460800
500000
interoctettimeout[Int] : should be in between 20 and 6000 seconds.
• https://192.168.1.12/configuration/eqbus
63
2CMC489001M0201
Revision: A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents