Technical Data

3.1 Technical Specifications

Specifications for G13 Ethernet gateway
Power supply
Voltage
Fuse
Frequency
Power consumption in standby
Power consumption in operation
Terminal wire area
Recommended tightening torque
RS-485
Baudrate
Terminal wire area solid
Terminal wire area stranded
Recommended tightening torque
M-Bus
M-Bus master
Protocol
Baudrate
Terminal wire area solid
Terminal wire area stranded
Recommended tightening torque
Mechanical
Enclosure material
Height
Width
Depth
Product weight
Environmental
Operating temperature range
Storage temperature range
Humidity
Resistance to fire and heat
Mechanical environment
Electromagnetic environment
Standards
LVD
EMC
G13
User Manual
100 - 240 V AC (-20% - +15%)
0.5 - 80 A
50 or 60 Hz ± 5%
10 W
Max. 20 W
2
0.75 - 1.5 mm
0.5 Nm
1200-500 000 bps
2
0.05 - 1.5 mm
2
0.05 - 1 mm
0.25 Nm
Supports up to 16 unit loads.
M-Bus
300 - 38400 bps
2
0.05 - 1.5 mm
2
0.05 - 1 mm
0.25 Nm
Polycarbonate
106 mm
70 mm
65 mm
190 g
-25°C to +70°C
-40°C to +85°C
75% yearly average, 95% on 30 days/year
650°C (IEC 60695-2-1)
Class M1 in accordance with the Measuring Instrument Direc-
tive (MID), (2004/22/EC).
Class E2 in accordance with the Measuring Instrument Direc-
tive (MID), (2004/22/EC).
IEC/EN 60950-1
IEC/EN 61000-6-3, IEC/EN 61000-6-2
13
2CMC489001M0201
Revision: A