ABB G13 User Manual page 197

Table of Contents

Advertisement

JSON Communication
Description
Note
There are 4 pulse outputs.
Any pulse output can be assigned to any port.
Thus each of pulse description to include id field specifying pulse output
1,2,3 or 4.
Then specify port to assign.
Pulse output can be turned off by specifying port number as 255.
Example
G13
User Manual
"frequency": 10000,
"energytype": 3
}
]
}
pulse[Array of Objects]
• length[int] - Pulse length in milliseconds
• frequency[int] - Pulse frequency in impulses per second
• energytype[string] - Pulse energy type
Energy types are:
active_import = 0
active_export = 1
reactive_import = 2
reactive_export = 3
turned_off = 4
invalid = 0xff
port[int] - Port number[1...4 or 255(Turned Off)]
• https://192.168.1.12/meters/ABB_8/io/pulse