Cleanliness; Cooling System; Esd Prevention - H3C RA100 Installation Manual

Table of Contents

Advertisement

Table 1 Temperature and humidity requirements
Temperature
–20°C to +60°C (–4°F to +140°F)

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points, especially when indoor relative humidity is low. In the worst
case, electrostatic adsorption can cause communication failure.
Table 2 Dust concentration limit in the equipment room
Substance
Dust particles
NOTE:
Dust diameter ≥ 5 µm
The equipment room must also meet limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in
Table 3 Harmful gas limits in an equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

Cooling system

To ensure good ventilation, follow these guidelines:
Maintain a minimum clearance of 10 cm (3.94 in) around the air inlet and outlet vents.
Make sure the installation site has a good ventilation system.

ESD prevention

WARNING!
Check the resistance of the ESD wrist strap for safety. The resistance reading should be in the range
of 1 to 10 megohm (Mohm) between a human body and the ground.
To prevent electrostatic discharge (ESD), follow these guidelines:
Make sure the router and the floor are reliably grounded.
Take dust-proof measures for the equipment room.
Maintain the humidity and temperature levels in the acceptable range.
Always wear an ESD wrist strap and an ESD garment when touching a circuit board or
transceiver module.
Relative humidity
5% to 90%, noncondensing
Concentration limit (particles/m
4
≤ 3 x 10
(No visible dust on the tabletop in three days)
Table
3.
Maximum concentration (mg/m
0.2
0.006
0.05
0.01
2
3
)
3
)