Operating Altitude; Cleanliness; Emi - H3C SR8800-F Series Installation Manual

Hide thumbs Also See for SR8800-F Series:
Table of Contents

Advertisement

Operating altitude

Table 2 Operating altitude requirements
Item
Operating altitude

Cleanliness

Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of
metal components and contact points. In the worst case, electrostatic adsorption can cause
communication failure.
Table 3 Dust concentration limits in the equipment room
Substance
Dust particles
Corrosive gases can accelerate corrosion and aging of components. Make sure the corrosive gases
in the equipment room do not exceed the concentration limits as shown in
Table 4 Corrosive gas concentration limits in the equipment room
Gas
SO
2
H
S
2
Cl
2
HCI
HF
NH
3
O
3
NO
X

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the router and application
system, adversely affect the router in the following ways:
Capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE)
to filter interference from the power grid.
Specifications
≤ 4000 m (13123.36 ft) (available altitude)
≤ 3000 m (9842.52 ft) (certified altitude)
Particle diameter
≥ 0.5 µm
Average concentration (mg/m
0.3
0.1
0.1
0.1
0.01
1.0
0.05
0.5
3
Concentration limit
≤ 1.8 × 10
7
3
particles/m
Table
3
)
Maximum concentration (mg/m
1.0
0.5
0.3
0.5
0.03
3.0
0.1
1.0
4.
3
)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sr8803-fSr8805-fSr8808-fSr8812-f

Table of Contents