Maintenance; Replacing The Glass On A Manual Call Point; Resetting The Resettable Element On A Manual Call Point - Honeywell Gent Vigilon Compact Operating Instructions Manual

Voice alarm based fire detection and alarm system
Table of Contents

Advertisement

Maintenance

Replacing the glass on a Manual Call
Point
a.
Disengage the front cover from the call point
assembly using the end of the test key. Insert
the key into the slots 'E' and from the bottom
edge lift out the cover.
E
b.
Carefully remove broken glass.
&
Take appropriate
precautions when clearing broken
glass to prevent injury.
YELLOW
ARM
F
c.
Turn the test key such that the tab is at position
'F' and insert a new glass as shown.
d.
Hook the front cover onto the top edge of the
call point assembly and then push the bottom
edge down until it click shuts. Check both hooks
on the top of the front cover are locked onto the
call point assembly.
e.
Turn the test key anticlockwise one quarter of a
turn such that the glass is held under the yellow
arm.
GLASS
Vigilon
Cover
Test Key
S4-34891 Spare MCP glass (Pack of 10)
Resetting the resettable element on a
Manual Call Point
Slide the cover upwards to expose the key hole. Insert
the test key in the keyhole and turn it clockwise by
one quarter of a turn. Then turn the test key
anticlockwise by one quarter of a turn to reset the call
point element.
COMPACT VOICE ALARM